Sensor: Field replacement electrochemical, 4 year typical lifespan
Range: 0 to 200 ppm
Coverage Area: 5000 to 7000 sq.ft.typical.
Accuracy: ±2% of reading at the time of calibration.
Output Drift: <5% per year in air.
Temperature Limits: -4 to 122°F (-20 to 50°C).
Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C).
Humidity Limits: 15 to 90% RH constant 0 to 99% RH intermittent.
Response Time: < 45 seconds to 90% of final value.
Calibration: 15 turn span and zero adjustment potentiometers.
Housing: UV resistant polycarbonate
Output: Jumper able 4 to 20 mA (loop powered) or 2 to 10 V (load must be >50KΩ).
Power Requirements: Current Output: 18 to 28 VDC Voltage Output:18 to 28 VDC/VAC, reverse polarity protected.
Electrical Connection: Removable terminal block, includes two PG11 and one PG 16 knockouts for conduit fitting
Weight: 0.28 (0.11 kg).
Agency Approvals: CE.
- CO CMT 200 gas sensor can choose the output value by current or voltage, based on the rate of gas in the basement parking lot, auto maintenance workshop or mechanical workshop.
Please contact us through our hotline or send us an e-mail for more information. We are very pleased to serve you!